3M™ RJS-4-10FT Non Stock
printPrint
  1. pin-int

3M™ RJS-4-10FT

RJS-4-10FT Rejacketing Sleeve, 10 ft L, Rubber, Dark Gray

  • MPN: RJS-4-10FT
  • UPC: 054007431053
  • Min. Order Qty: 1
  • Quantity Interval: 1
  • loading loading
3M™ RJS-4-10FT

3M™ RJS Series rejacketing sleeves are designed so that 3M™ cold shrink QTII and QTIII silicone rubber termination applications can be used on 3/C (three conductor) medium voltage shielded power cables of tape shield, wire shield, armored and non-armored configurations. RJS rejacketing assemblies are a Series of silicone rubber insulators incorporating an inner expandable polyester braid designed to reduce sliding friction and deliver the insulator onto the cable. Rejacketing sleeves are designed to protect the phase legs (core) of 3/C shielded power cable from exposure to moisture, corrosion, ozone, ultra-violet radiation, physical contact and other hazards that are associated with termination operating environments. Rejacketing sleeves are designed to be used in conjunction with 3M™ cold shrink breakout boots and silicone rubber terminations.

3M™ Rejacketing Sleeve, Series: RJS, 10 ft L Size, Specifications: 1.02 to 1.28 in Dia Metallic Shield Range, 3.3 to 8 kV Voltage Range, 180 deg C, Rubber, Dark Gray

Series      :      RJS
Specifications      :      1.02 to 1.28 in Dia Metallic Shield Range, 3.3 to 8 kV Voltage Range
Temperature Rating      :      180 deg C
Size      :      10 ft L
Material      :      Rubber
Color      :      Dark Gray
  • Versatile installs quickly and accommodates a wide range of cable sizes
  • Simple hand application no need for special installation tools
  • No torches or heat source required
  • Excellent resistance to ozone and ultra-violet radiation
  • Good solvent resistance compatible with industry approved cable cleaners
  • Excellent thermal stability
  • High dry and wet insulation resistance
  • Excellent shelf life
  • Easy to adjust sleeve length adapts to variable equipment connection and mounting requirements
  • Used to protect shielded phase legs (cores) of 3/C medium voltage (35 kV and less) power cables after the jacket has been removed in preparation for terminating
  • Accommodate cable sizes ranging from 8 AWG (8 sq-mm) at 3.3 kV, 750 kcmil (325 sq-mm) at 35 kV
  • Available in 6 sizes to cover cable metallic shield Dia ranging from 0.43 in (10.9 mm) to 1.91 in (48.5 mm)
  • RJS Series sleeve assemblies can be field tested using normal cable testing procedures
  • Rejacketing sleeves are designed to protect the phase legs (core) of 3/C shielded power cable from exposure to moisture, corrosion, ozone, ultra-violet radiation, physical contact and other hazards that are associated with termination operating environments
  • Cold shrink QT-III and Q-TIII silicone rubber terminations can be used on 3/C (3-conductor) medium voltage shielded power cables of tape shield, wire shield, armored and non-armored configuration
  • 10 ft L linear
  • pdfCatalog https://assets.unilogcorp.com/2/ITEM/DOC/3M_054007_43099_Brochure.pdf
  • pdfInstruction/Installation Manual https://assets.unilogcorp.com/2/ITEM/DOC/IDW_DOCUMENT_4ab08b40367db126cc27777399f6c5b836642e91cab856e472cd83ab780e7cf4.pdf
  • pdfLine Drawing https://assets.unilogcorp.com/2/ITEM/DOC/IDW_DOCUMENT_9ebbb0bb82459d1d6032c40385ac3d454bcfe7cc47e50891de84e9654ccd93f1.pdf
  • pdfSpecification Sheet https://assets.unilogcorp.com/2/ITEM/DOC/IDW_DOCUMENT_b472e792f1c6340aecd92560cf4e8878096852bdd22a6d4479869e500e1eb3c7.pdf