Non Stock
printPrint
  1. pin-int

Weidmuller 1176020000

Weidmuller 1176020000 Isolation Amplifier, 0 to 5/0 to 10 VDC Input, 0 to 5/0 to 10 VDC Output, 1.2 W Power Rating

  • MPN: 1176020000
  • UPC: 032248970081
  • Min. Order Qty: 1
  • Quantity Interval: 1
  • loading loading
Weidmuller 1176020000

The universal input and output parameters can be configured as required using the DIP switches. The input/ output channel(s) and power supply have 2.5 kV of electrical isolation. The universal ACT20M-AI-AO-S supply isolator can feed power directly from the input loop signal to passive sensors. ACT20M-AI-2AO-S with 4-way isolation is designed as a signal splitter. The input signal is doubled on the output side. It can be transmitted simultaneously to a controller and an external display. The power supply can be easily and quickly installed using the CH20M DIN rail bus. The power can be supplied using any ACT20M module (up to 20 devices) or a separate ACT20 supply module (up to 200 devices).

Weidmuller Isolation Amplifier, 0 to 5/0 to 10 VDC Input, 0 to 5/0 to 10 VDC Output, 0 to 20/4 to 20 mA Input Current, 0 to 20/4 to 20 mA Output Current, 1.2 W Power, Thread Connection, DIN Rail Mounting, -25 to 70 deg C, 7 ms Response, <0.05 % Accuracy, 4.429 in H x 0.24 in W x 4.5 in D Dimensions

Accuracy      :      <0.05 %
Connection Type      :      Thread
Dimensions      :      4.429 in H x 0.24 in W x 4.5 in D
Input Current      :      0 to 20/4 to 20 mA
Mounting Type      :      DIN Rail
Output Current      :      0 to 20/4 to 20 mA
Response Time      :      7 ms
Temperature Rating      :      -25 to 70 deg C
Input Voltage      :      0 to 5/0 to 10 VDC
Output Voltage      :      0 to 5/0 to 10 VDC
Power Rating      :      1.2 W
  • 40 deg C humidity
  • 17 VDC at 20 mA sensor supply
  • 1.5 V voltage drop, current input
  • 100 Hz cut-off frequency (-3 dB)
  • 300 Ohm, per channel, at max 23 mA load impedance current
  • 10 kOhm load impedance voltage
  • 3-way galvanic isolation
  • DIP switch configuration
  • 0.84 W power consumption
  • The configurable DC isolating amplifier ACT20M-AI-AO-S isolates and converts analogue standard signals
  • An analogue input signal is linearly converted into an analogue output signal and galvanically isolated, 2 galvanically isolated outputs (4-way isolation)
  • The input can also be operated as an active current loop
  • pdfSpecification Sheet https://uat.south.electrozad.com//ASSETS/DOCUMENTS/ITEMS/EN/Weidmuller_1176020000_Data_Sheet.pdf