PGR-3100 Ground Fault Indication System With LED's, 600 VAC, Panel Mount
| Branch Name | Available |
|---|
The PGR-3100 indicates the presence of voltage on each phase of a 3-ph system. The LEDs on the panel illuminate when voltage is present. When A ground fault occurs, the voltage on the faulted phase reduces to ground potential, causing the LEDs for the faulted phase to dim. On A resistance grounded or ungrounded system the LEDs for the unfaulted phases become brighter. Ungrounded ac systems are required by the national electrical code (NEC®) Article 250.21(B) and the Canadian electrical code part 1, section 10-106 (2) to have ground detectors, such as the PGR-3100, installed on the system. External potential transformers (PTs) can be used to step down system voltage, allowing the PGR-3100 to be applied to a ny system voltage. PTs are not required for system voltages up to 600 VAC.
Littelfuse® POWR-GARD® Ground Fault Indication System, Series: PGR-3100, 600 VAC, Panel Mount, 3.5 in H x 4.3 in W x 2.1 in D
| Dimensions | : | 3.5 in H x 4.3 in W x 2.1 in D |
| Series | : | PGR-3100 |
| Voltage Rating | : | 600 VAC |
| Mounting Type | : | Panel |