Hoffman ClimaGuard™ WCHE14916002 MCLHE WCHE14 Heat Exchanger, 115 VAC, 2 A, 200 W Power Rating, NEMA 15/IP55 Enclosure, 855 cfm at 50/60 Hz Internal Loop Air Flow
| Branch Name | Available |
|---|
Climaguard Air-to-Water Indoor Heat Exchanger removes heat from an enclosure by flowing enclosure hot air across a water-cooled exchanger core. Inside cabinet temperatures can range from 10 to 50 deg C (50 to 122 deg F) while ambient operating temperatures can range from 10 to 70 C (50 to 158 F). Includes a condensation recovery system and condensation discharge pipe. These units do require an available cooled water source.
Hoffman ClimaGuard™ Heat Exchanger, Series: MCLHE WCHE14, 115 VAC, 2 A, 200 W, 50/60 Hz, NEMA 15/IP55, 855 cfm at 50/60 Hz Internal Loop, 22861 Btu/hr, 50 to 158 deg F Ambient, Mild Steel/Sheet Metal, Light Gray, 43.34 in H x 19.72 in W x 11.81 in D
| Ambient Temperature Rating | : | 50 to 158 deg F |
| Capacity | : | 22861 Btu/hr |
| Color | : | Light Gray |
| Dimensions | : | 43.34 in H x 19.72 in W x 11.81 in D |
| Frequency Rating | : | 50/60 Hz |
| Material | : | Mild Steel/Sheet Metal |
| Series | : | MCLHE WCHE14 |
| Voltage Rating | : | 115 VAC |
| Amperage Rating | : | 2 A |
| Power Rating | : | 200 W |
| Enclosure Type | : | NEMA 15/IP55 |
| Air Flow Rate | : | 855 cfm at 50/60 Hz Internal Loop |